Genset MP 30 I with FPT – Fiat / Iveco is suitable to take 100% load in one step. We tested first of FPT – Fiat / Iveco F32 series engine with electronic speed regulation with perfect results. Genset MP 30 I is capable to take one step 100% of PRP. Maximum deflection of frequency is 5 % of nominal value. After 1.05 s was deflection 1% of nominal value. Maximum decrease of voltage is 10% of nominal value. After 1.05 s decrease not exceed 1% of nominal value.